Recommendations for maximum current for cables:
Copper cable diameter | Power distribution | Equipment cables |
0.5 mm2 | - | 3A |
0.75 mm2 | 7.6A | 6A |
1.0 mm2 | 10.4A | 10A |
1.5 mm2 | 13.5A | 16A |
2.5 mm2 | 18.3A | |
4 mm2 | 25A | |
6 mm2 | 32A |
Data on different AWG cable sizes:
AWG Feet/Ohm Ohms/100ft Ampacity* mm^2 Meters/Ohm Ohms/100M 10 490.2 .204 30 2.588 149.5 .669 12 308.7 .324 20 2.053 94.1 1.06 14 193.8 .516 15 1.628 59.1 1.69 16 122.3 .818 10 1.291 37.3 2.68 18 76.8 1.30 5 1.024 23.4 4.27 20 48.1 2.08 3.3 0.812 14.7 6.82 22 30.3 3.30 2.1 0.644 9.24 10.8 24 19.1 5.24 1.3 0.511 5.82 17.2 26 12.0 8.32 0.8 0.405 3.66 27.3 28 7.55 13.2 0.5 0.321 2.30 43.4